@article{article_471714, title={Experimental Performance Analysis of a Groundwater Heat Pump System in Erzincan, Turkey}, journal={Erzincan University Journal of Science and Technology}, volume={12}, pages={1254–1265}, year={2019}, DOI={10.18185/erzifbed.471714}, author={Kalkan, Orhan and Kaya, Mehmet}, keywords={Energy,Heat pump,Groundwater,Refrigerant,COP}, abstract={

In this study, a place with a floor area of 80 m² in Erzincan was heated by the Groundwater Heat Pump (GWHP). In this application experimentally investigated, energy and performance analysis of the heat pump and the entire system were performed. Evaporator water flow, condenser water flow and air flows of fan-coil devices was fixed at certain values. Then the measurements have been made under 9 different conditions consisting of these parameters. In the condition which the highest yield is obtained, performance coefficients of the heat pump (  and the system (  were determined 4.27 and 2.92, respectively. In this condition, the average amount of heat discharged from the condenser was calculated to be 14.3 kW. On the other hand, Groundwater quality and temperature that is an important criterion of the GWHP system was found to applicable to Erzincan. 

}, number={3}, publisher={Erzincan Binali Yildirim University} }